Model: GSA-CC1S
Category: Voice Evacuation
Brand: Kidde - Vigilant
Dealer pricingGSA-CC1Sand MCC1S Synchronization Output Modules are intelligent analog addressable devices that form part of Kidde’s Signature line of products. The actual operation of the GSA-CC1S and MCC1S is determined by the “personality code” selected by the installer, which is downloaded to the module from the Signature loop controller during system configuration.
Depending on their assigned personality, Synchronization Output Modules may be used as a signal power riser selector to provide synchronization of fire alarm signals across multiple zones, or for connecting, upon command from the loop controller, supervised Class B signal or telephone circuits to their respective power inputs. The power inputs may be polarized 24 Vdc to operate audible and visible signal appliances or 25 and 70 VRMS to operate audio evacuation speakers and firefighter’s telephones.
The GSA-CC1S mounts to a standard North American two-gang electrical box, making it ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module.
Application/Usage | Security |
Brand Name | Edwards Signaling |
Manufacturer | UTC Fire & Security Company |
Model | GSA-CC1S |
Product Type | Strobe Synchronization Module |
Vendor Name | Kidde - Vigilant |